3401.17.L
| H+S | |
|---|---|
| Side of bulkhead | protected side |
| Moisture resistance according | MIL-STD-202, Method 106 |
| Vibration according | MIL-STD-202, Method 204, Cond. D |
| bre.att-ter-frequency-range-max | 1000 |
| bre.att-ter-frequency-range-min | 0 |
| Storage temperature | -40 °C ... 85 °C |
| Residual pulse energy (typ.) | 350 µJ (test pulse 4 kV 1.2/50 µs; 2 kA 8/20 µs) |
| Thermal shock according | MIL-STD-202, Method 107, Cond. B |
| Insertion loss typical | 0.1 dB |
| Product code | 3401.17.L |
| Main path connectors | Port 1: unprotected, N jack (female)Port 2: protected, N jack (female) |
| Housing material / plating | Brass / SUCOPLATE (R) Plating |
| Electrical remarks | Data refer to GDT 9071.99.0547, 230 V |
| Ingress protection (IP Rating) | IP20 |
| Details | CAS: 7439-92-1 Lead |
| The EMP configuration is triaxial | YES |
| Mounting and grounding | MH74 (bulkhead mounting) |
| Residual pulse voltage (typ.) | 650 V (test pulse 4 kV 1.2/50 µs; 2 kA 8/20 µs) |
| Return loss typical | 20.8 dB |
| Surge current handling capability | 30 kA single, 20 kA multiple (test pulse 8/20 µs) |
| Center contact, material / plating | Port 1: Copper Beryllium Alloy / Gold Plating (without Nickel underplating)Port 2: Copper Beryllium Alloy / Gold Plating (without Nickel underplating) |
| EMP can be install reversed | YES |
| Mating cycles | 500 |
| Weight | 330 g |
| Exemptions | 6c |
| Gas tube | Yes DC, GDT not included |
| Directive | RoHS 2011/65/EU and (EU) 2015/863 |
| Impedance | 50 Ω |
| Operation temperature | -40 °C ... 85 °C |
| Rating | Compliant with exemption , Contains one or more SVHC >0,1% |
| Product description | GDT technology up to 1.0 GHz |
| Frequency frame | 0 MHz to 1000 MHz |
| Regulation | REACH 1907/2006 Article 33 SVHC |
| CW power frame | 150 |
