H+S |
Side of bulkhead |
protected side |
Moisture resistance according |
MIL-STD-202, Method 106 |
Vibration according |
MIL-STD-202, Method 204, Cond. D |
Insertion loss |
≤ 0.2≤ 0.2 dB |
bre.att-ter-frequency-range-max |
6000 |
bre.att-ter-frequency-range-min |
0 |
Storage temperature |
-40 °C ... 85 °C |
Residual pulse energy (typ.) |
250 µJ (test pulse 4 kV 1.2/50 µs; 2 kA 8/20 µs) |
Thermal shock according |
MIL-STD-202, Method 107, Cond. B |
Insertion loss typical |
≤ 0.3 dB |
Product code |
3406.17.0009 |
Main path connectors |
Port 1: unprotected, N jack (female)Port 2: protected, N jack (female) |
Housing material / plating |
Brass / Silver / Gold Plating |
Electrical remarks |
Return Loss 5600 - 5800 MHz typ > 20 dB |
Ingress protection (IP Rating) |
Mated / IP67, according to IEC 60529 |
Static spark voltage |
200 V, +/- 25 % (@ 100 V/s) |
Details |
CAS: 7439-92-1 Lead |
Mounting and grounding |
MH24 (bulkhead mounting) |
Return loss typical |
≥ 15 dB , ≥ 20≥ 18.5 dB |
Surge current handling capability |
10 kA single, 5 kA multiple (test pulse 8/20 µs) |
Center contact, material / plating |
Port 1: Copper Beryllium Alloy / Gold Plating (without Nickel underplating)Port 2: Copper Beryllium Alloy / Gold Plating (without Nickel underplating) |
EMP can be install reversed |
YES |
Frequency range |
0 MHz ... 5600 MHz5600 MHz ... 5800 MHz |
Mating cycles |
500 |
Inline design |
YES |
Weight |
90 g |
Exemptions |
6c |
Gas tube |
Yes DC, GDT included, not replaceable |
Directive |
RoHS 2011/65/EU and (EU) 2015/863 |
Impedance |
50 Ω |
Operation temperature |
-40 °C ... 85 °C |
Rating |
Compliant with exemption , Contains one or more SVHC >0,1% |
Product description |
Slim Line GDT technology |
Frequency frame |
0 MHz to 6000 MHz |
Regulation |
REACH 1907/2006 Article 33 SVHC |
CW power frame |
50 |