3406.17.0028
H+S | |
---|---|
Side of bulkhead | protected side |
Gas tube | Yes DC, GDT included, not replaceable |
Moisture resistance according | MIL-STD-202, Method 106 |
Impedance | 50 Ω |
Vibration according | MIL-STD-202, Method 204, Cond. A |
Storage temperature | -40 °C ... 85 °C |
Operation temperature | -40 °C ... 85 °C |
Residual pulse energy (typ.) | 250 µJ LEMP (test pulse 4 kV 1.2/50 µs; 2 kA 8/20 µs) |
Product description | Slim Line GDT technology |
Thermal shock according | MIL-STD-202, Method 107, Cond. B |
Insertion loss typical | ≤ 0.2 dB |
Product code | 3406.17.0028 |
Main path connectors | Port 1: unprotected, N plug (male)Port 2: protected, N jack (female) |
Housing material / plating | Brass / Tri-metal Plating |
Ingress protection (IP Rating) | IP68 |
Static spark voltage | 90 V, +/- 20 % (@ 100 V/s) |
Frequency frame | 0 MHz to 4000 MHz |
Mounting and grounding | MH24 (bulkhead mounting) |
Return loss typical | ≥ 20 dB |
Surge current handling capability | 10 kA single, 5 kA multiple (test pulse 8/20 µs) |
Center contact, material / plating | Port 1: Bronze / Gold PlatingPort 2: Bronze / Gold Plating |
EMP can be install reversed | YES |
Mating cycles | 500 |
CW power frame | ≤ 21 W |
Inline design | YES |
Weight | 76 g |